Before installation, start-up and maintenance work on the drive:
Stop the drive.
Disconnect the motor from the drive with a safety switch or by other means.
If you cannot disconnect the motor, make sure that the motor cannot rotate during
work. Make sure that no other system, like hydraulic crawling drives, can rotate
the motor directly or through any mechanical connection like belt, nip, rope, etc.
Do the steps in section Electrical safety precautions (page 21).
Install temporary grounding to the drive output terminals (T1/U, T2/V, T3/W).
Connect the output terminals together as well as to the PE.
During the start-up:
Make sure that the motor cannot run overspeed, for example, driven by the load.
Motor overspeed causes overvoltage that can damage or destroy the capacitors
in the intermediate circuit of the drive.
Safety in operation
WARNING!
Make sure that the motor cannot run overspeed, for example, driven by the
load. Motor overspeed causes overvoltage that can damage or destroy the
capacitors in the intermediate circuit of the drive.
Safety instructions 25

Table of Contents

Other manuals for ABB ACS880-07

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880-07 and is the answer not in the manual?

ABB ACS880-07 Specifications

General IconGeneral
CategoryDC Drives
EfficiencyUp to 98%
Power Range0.75 kW to 5600 kW
Supply Voltage380 to 690 V AC
Output Voltage380 V to 690 V AC
Cooling MethodAir-cooled
Enclosure ClassIP21
MountingWall-mounted
Communication ProtocolsEthernet, Modbus, Profibus, CANopen

Related product manuals