Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective pack-
age
Storage
in the protective pack-
age
Operation
installed for stationary
use
--0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, con-
tact ABB.
Installation site altitude
Output derated above
1000 m (3281 ft).
-40 … +70 °C-40 … +70 °C0 … +40 °C
(+32 … +104 °F). No con-
densation allowed.
Air temperature
(-40 … +158 °F)(-40 … +158 °F)
Output derated in the
range +40 … +50 °C
(+104 … +122 °F).
For UL and CSA compli-
ant installations, the
maximum surrounding
air temperature is 40 °C
(104 °F).
Max. 95%Max. 95%Max. 95%Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
IEC 60721-3-2:1997IEC 60721-3-1:1997IEC/EN 60721-3-3:2002Contamination
Chemical gases: Class
2C2
Chemical gases: Class
1C2
Chemical gases: Class
3C2
Solid particles: Class 2S2Solid particles: Class 1S3
(packing must support
this, otherwise 1S2)
Solid particles: Class 3S2
(3S1 with IP20). No con-
ductive dust allowed.
2Pollution degree
IEC/EN 60664-1
IEC/EN 60721-3-2:1997IEC/EN 60721-3-1:1997IEC/EN 60721-3-3:2002Vibration
2…9 Hz: max. 3.5 mm
amplitude
10…57 Hz: max.
0.075 mm amplitude
10…57 Hz: max.
0.075 mm amplitude
IEC/EN 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008 9…200 Hz: 10 m/s
2
(32.8 ft/s
2
)
57…150 Hz: 1
g
57…150 Hz: 1
g
Units with marine con-
struction (option +C121):
Max. 1 mm (0.04 in)
(5 … 13.2 Hz), max. 0.7
g
(13.2 … 100 Hz) sinusoid-
al
With packing max.
100 m/s
2
(328 ft/s
2
)
11 ms
With packing max.
100 m/s
2
(328 ft/s
2
)
11 ms
Not allowedShock
IEC 60068-2-27:2008, EN
60068-2-27:2009
Technical data 239