DescriptionTerminal
Temp fault
2)
(0 = overtemperature)DI11
Run enable
2)
(1 = run enable)DI22
MCB feedback
3)
(0 = main contactor/breaker open)DI33
Auxiliary circuit breaker fault
2)
DI44
Not in use by default. Can be used for eg. earth fault monitoring.DI55
Reset
2)
(0 -> 1 = fault reset)DI66
Not in use by default. Can be used for eg. emergency stop.DIIL7
Digital input/outputsXDIO
Not in use by defaultDIO11
Not in use by defaultDIO22
Digital input/output groundDIOGND3
Digital input/output groundDIOGND4
Auxiliary voltage outputXD24
+24 V DC 200 mA
5)
+24VD5
Digital input groundDICOM6
+24 V DC 200 mA
5)
+24VD7
Digital input/output groundDIOGND8
Ground selection switch
6)
DICOM=DIOGND
Analog inputs, reference voltage outputXAI
10 V DC,
R
L
1…10 kohm+VREF1
-10 V DC,
R
L
1…10 kohm-VREF2
GroundAGND3
Not in use by default. 0(2)…10 V,
R
in
> 200 kohm
7)
AI1+4
AI1-5
Not in use by default. 0(4)…20 mA,
R
in
= 100 ohm
8)
AI2+6
AI2-7
AI1 current/voltage selection switchAI1
AI2 current/voltage selection switchAI2
Analog outputsXAO
Zero (no signal indicated)
2)
0…20 mA,
R
L
< 500 ohm
AO11
AGND2
Zero (not signal indicated)
2)
0…20 mA,
R
L
< 500 ohm
AO23
AGND4
External power inputXPOW
24 V DC, 2.05 A
+24VI1
GND2
+24VI3
GND4
Not in use in supply unitsX12
Control panel connectionX13
Control units of the drive 147