DescriptionTerminal
XRO3: Fault (-1) (Energized = No fault)
250 V AC / 30 V DC, 2 A
Norm. closedNC331
CommonCOM332
Norm. openNO333
Relay output 4XRO4
XRO4: Not supported
Norm. closedNC441
250 V AC / 30 V DC, 2 A
CommonCOM442
Norm. openNO443
Safe torque offXSTO
XSTO: Factory connection. Both circuits (power module, control unit) must
be closed for the drive to start (STO1 and STO2 must be connected to OUT).
Refer to chapter The Safe torque off function (page 307).
OUT1
SGND2
STO13
STO24
Safe torque off connection (to inverter modules)XSTO OUT
XSTO OUT: Safe torque off output to inverter modules
OUT15
SGND6
OUT27
SGND8
Digital inputsXDI
Stop (0) / Start (1)DI11
Forward (0) / Reverse (1)DI22
ResetDI33
Acceleration & deceleration select
1)
DI44
Constant speed 1 select (1 = on)
2)
DI55
Not in use by default.DI66
Run enable
3)
DIIL7
Digital input/outputsXDIO
Output: ReadyDIO11
Output: RunningDIO22
Digital input/output groundDIOGND3
Digital input/output groundDIOGND4
Auxiliary voltage outputXD24
+24 V DC 200 mA
4)
+24VD5
Digital input groundDICOM6
+24 V DC 200 mA
4)
+24VD7
Digital input/output groundDIGND8
Ground selection switch. Determines whether DICOM is separated from
DIOGND (ie. common reference for digital inputs floats). ON: DICOM con-
nected to DIOGND. OFF: DICOM and DIOGND separate.
DICOM=DIOGND
160 Control units of the drive