436 Parameters
79.53 Overload curve
point 3
Defines overload curve point 3 load limit active at
corresponding speed set in parameter 79.03 Load curve
speed point 3.
0.00
-30000.00...
30000.0 0
Overload curve point 3. 10 = 1
79.54 Overload curve
point 4
Defines overload curve point 4 load limit active at
corresponding speed set in parameter 79.04 Load curve
speed point 4.
0.00
-30000.00...
30000.0 0
Overload curve point 4. 10 = 1
79.55 Overload curve
point 5
Defines overload curve point 5 load limit active at
corresponding speed set in parameter 79.05 Load curve
speed point 5.
0.00
-30000.00...
30000.0 0
Overload curve point 5. 10 = 1
79.58 Overload curve
scale coef
Defines multiplier coefficient applied to the overload limit
calculated out of the overload curve.
1.000
-30.000...30.000 Overload curve scale coef. 100 = 1
79.59 Overload curve
offset
Defines offset additive value applied to the overload limit
calculated out of the overload curve.
0.00
-30000.00...
30000.00
Overload curve offset. 10 = 1
79.61 Overload recovery
speed
Defines speed reference used in course of the overload
recovery routine.
10.00
0.00...600.00 Hz Overload safe speed. 10 = 1Hz
79.62 Overload recovery
speed time
Defines time for the overload recovery routine to stay active. 60.0
0.0...30000.0 s Overload safe speed time. 1 = 1s
79.80 Underload actual
limit
Displays currently active underload limit. 0.00
-30000.00...
30000.00
Underload actual limit. 10 = 1
79.81 Underload trip
count down
Displays the delay time remaining before underload condition
response is triggered.
0.0
0.0...30000.0 s Underload actual limit. 10 = 1s
79.89 URT recovery
attempts
Displays the number of underload recovery attempts made. 0
0...100 URT recovery attempts. 1 = 1
79.90 Overload actual
limit
Displays currently active overload limit. 0.00
-30000.00...
30000.00
Overload actual limit. 10 = 1
79.91 Overload trip count
down
Displays the delay time remaining before overload condition
response is triggered.
0.0
0.0...30000.0 s Overload trip count down. 10 = 1s
79.99 Load protection
status word
Displays the status word for the load protection function. 0b0000
No. Name/Value Description Def/FbEq16