630 Fieldbus control through the embedded fieldbus interface (EFB)
Error code registers (holding registers 400090…400100)
These registers contain information about the last query. The error register is cleared
when a query has finished successfully.
Reference Name Description
89 Reset Error Registers 1 = Reset internal error registers (91…95).
90 Error Function Code Function code of the failed query.
91 Error Code Set when exception code 04h is generated (see table
above).
00h No error
02h Low/High limit exceeded
03h Faulty Index: Unavailable index of an array
parameter
05h Incorrect Data Type: Value does not match the
data type of the parameter
65h General Error: Undefined error when handling
query
92 Failed Register The last register (discrete input, coil, or holding
register) that failed to be read or written.
93 Last Register Written
Successfully
The last register that was written successfully.
94 Last Register Read
Successfully
The last register that was read successfully.