92 Program features
In the ACS880, the following settings are made:
• 92.01 Encoder 1 type = HTL
• 92.02 Encoder 1 source = Module 1
• 92.10 Pulses/revolution = 2048
• 92.13 Position estimation enable = Enable
• 90.51 Load feedback selection = Encoder 1
• 90.63 Feed constant numerator = 8192 (ie. 4 × value of 92.10, as the received
number of pulses is 4 times nominal. See also parameter 92.12 Resolver
polepairs)
• The desired “data out” parameter is set to Other – 90.58 Pos counter init value
int (32-bit format). Only the high word needs to be specified – the subsequent
data word is reserved for the low word automatically.
• The desired sources (such as digital inputs or user bits of the control word) are
selected in 90.67 Pos counter init cmd source and 90.69 Reset pos counter
init ready.
In the PLC, if the initial value is set in 32-bit format using low and high words
(corresponding to ACS800 parameters POS COUNT INIT LO and POS COUNT INIT
HI), enter the value 66770 into these words as follows:
Eg. PROFIBUS:
• FBA data out x = POS COUNT INIT HI = 1 (as bit 16 equals 66536)
• FBA data out (x + 1) = POS COUNT INIT LO = 1234.
ABB Automation using DDCS communication, eg.:
• Data set 12.1 = POS COUNT INIT HI
• Data set 12.2 = POS COUNT INIT LO
To test the configuration of the PLC, initialize the position counter with the encoder
connected. The initial value sent from the PLC should immediately be reflected by
90.07 Load position scaled int in the drive. The same value should then appear in the
PLC after having been read from the drive.
Settings
Parameter groups 90 Feedback selection (page 451), 91 Encoder module settings
(page 460), 92 Encoder 1 configuration (page 463) and 93 Encoder 2 configuration
(page 470).
Jogging
The jogging function enables the use of a momentary switch to briefly rotate the
motor. The jogging function is typically used during servicing or commissioning to
control the machinery locally.
Two jogging functions (1 and 2) are available, each with their own activation sources
and references. The signal sources are selected by parameters 20.26 Jogging 1 start
source and 20.27 Jogging 2 start source. When jogging is activated, the drive starts
and accelerates to the defined jogging speed (22.42 Jogging 1 ref or 22.43 Jogging 2