Loading...
410 Parameters
61.152 INU-LSU data set
10 data 2 sel
Preselects the data to be sent as word 2 of data set 10 to the
other converter.
See also parameter 61.202 INU-LSU data set 10 data 2
value.
For the selections, see parameter 61.151 INU-LSU data set
10 data 1 sel.
DC voltage
reference
61.153 INU-LSU data set
10 data 3 sel
Preselects the data to be sent as word 3 of data set 10 to the
other converter.
See also parameter 61.203 INU-LSU data set 10 data 3
value.
For the selections, see parameter 61.151 INU-LSU data set
10 data 1 sel.
Reactive
power
reference
61.201 INU-LSU data set
10 data 1 value
Displays (in integer format) the data to be sent to the other
converter as word 1 of data set 10.
If no data has been preselected by 61.151 INU-LSU data set
10 data 1 sel, the value to be sent can be written directly into
this parameter.
0
0…65535 Data to be sent as word 1 of data set 10.
61.202 INU-LSU data set
10 data 2 value
Displays (in integer format) the data to be sent to the other
converter as word 2 of data set 10.
If no data has been preselected by 61.152 INU-LSU data set
10 data 2 sel, the value to be sent can be written directly into
this parameter.
0
0…65535 Data to be sent as word 2 of data set 10.
61.203 INU-LSU data set
10 data 3 value
Displays (in integer format) the data to be sent to the other
converter as word 3 of data set 10.
If no data has been selected by 61.153 INU-LSU data set 10
data 3 sel, the value to be sent can be written directly into this
parameter.
0
0…65535 Data to be sent as word 3 of data set 10.
62
62 D2D and DDCS
receive data
Mapping of data received through the DDCS link.
See also parameter group 60 DDCS communication.
62.01 M/F data 1
selection
(Follower only) Defines a target for the data received as word
1 from the master through the master/follower link.
See also parameter 62.25 MF data 1 value.
None
None None. 0
CW 16bit Control Word (16 bits) 1
Ref1 16bit Reference REF1 (16 bits) 2
Ref2 16bit Reference REF2 (16 bits) 3
Other Source selection (see Terms and abbreviations on page 148). -
62.02 M/F data 2
selection
(Follower only) Defines a target for the data received as word
2 from the master through the master/follower link.
See also parameter 62.26 MF data 2 value.
For the selections, see parameter 62.01 M/F data 1 selection.
None
62.03 M/F data 3
selection
(Follower only) Defines a target for the data received as word
3 from the master through the master/follower link.
See also parameter 62.27 MF data 3 value.
For the selections, see parameter 62.01 M/F data 1 selection.
None