Application macros 137
Default parameter settings for the PID control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in Parameter listing (page 152).
Note: The macro selection does not affect parameter group 41 Process PID set 2.
Parameter
PID control macro default
No. Name
12.27 AI2 min 4.000
19.11 Ext1/Ext2 selection DI3
20.01 Ext1 commands In1 Start
20.04 Ext1 in2 source Not selected
20.06 Ext2 commands In1 Start
20.08 Ext2 in1 source DI6
20.12 Run enable 1 source DI5
22.12 Speed ref2 source PID
22.22 Constant speed sel1 DI4
23.11 Ramp set selection Acc/Dec time 1
31.11 Fault reset selection Not selected
40.07 Set 1 PID operation mode On when drive running
40.08 Set 1 feedback 1 source AI2 scaled
40.11 Set 1 feedback filter time 0.040 s
40.35 Set 1 derivation filter time 1.0 s
40.60 Set 1 PID activation source Follow Ext1/Ext2 selection