238 Parameters
20.07 Ext2 start trigger
type
Defines whether the start signal for external control location
EXT2 is edge-triggered or level-triggered.
Note: This parameter is only effective when parameter 20.06
Ext2 commands is set to In1 Start, In1 Start; In2 Dir, In1 Start
fwd; In2 Start rev, or Control panel.
Edge
Edge The start signal is edge-triggered. 0
Level The start signal is level-triggered. 1
20.08 Ext2 in1 source Selects source 1 for parameter 20.06 Ext2 commands.
For the available selections, see parameter 20.03 Ext1 in1
source.
Not selected
20.09 Ext2 in2 source Selects source 2 for parameter 20.06 Ext2 commands.
For the available selections, see parameter 20.03 Ext1 in1
source.
Not selected
20.10 Ext2 in3 source Selects source 3 for parameter 20.06 Ext2 commands.
For the available selections, see parameter 20.03 Ext1 in1
source.
Not selected
20.11 Run enable stop
mode
Selects the way the motor is stopped when the run enable
signal switches off.
The source of the run enable signal is selected by parameter
20.12 Run enable 1 source.
Coast
(95.20 b10)
Coast Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING! If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
0
Ramp Stop along the active deceleration ramp. See parameter
group 23 Speed reference ramp on page 257.
1
Torque limit Stop according to torque limits (parameters 30.19 and 30.20). 2
20.12 Run enable 1
source
Selects the source of the external run enable signal. If the run
enable signal is switched off, the drive will not start. If already
running, the drive will stop according to the setting of
parameter 20.11 Run enable stop mode
.
1 = Run enable signal on.
Note: The warning that indicates a missing signal can be
suppressed using parameter 20.30 Enable signals warning
function.
See also parameter 20.19 Enable start command.
DIIL
(95.20 b10);
Selected
(95.20 b5);
DI5
(95.20 b9)
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
FBA A MCW bit 3 Control word bit 3 received through fieldbus interface A. 30
EFB MCW bit 3 Control word bit 3 received through the embedded fieldbus
interface.
32
No. Name/Value Description Def/FbEq16

Table of Contents