Parameters 239
DIIL DIIL input (10.02 DI delayed status, bit 15). 33
Active control
source MCW bit 3
Control word bit 3 received from the active control source.
Notes:
If the drive is running in fieldbus control, switching bit 3 off
effectively removes both the start and run enable signals.
In this case, the stop mode is determined by either 20.11
Run enable stop mode or 21.03 Stop mode, whichever
mode has higher priority. The order of stop modes from
highest to lowest priority is CoastTorque limitRamp.
In case the active source is the control panel, PC tool or
drive I/O, the run enable signal is always on.
34
Other [bit] Source selection (see Terms and abbreviations on page 148). -
20.19 Enable start
command
Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command is
inhibited. (Switching the signal off while the drive is running
will not stop the drive.)
Notes:
If a level-triggered start command is on when the start
enable signal switches on, the drive will start. (An edge-
triggered start signal must be cycled for the drive to start.)
See parameters 20.02 Ext1 start trigger type and 20.07
Ext2 start trigger type.
The warning that indicates a missing signal can be
suppressed using parameter 20.30 Enable signals warning
function.
See also parameter 20.12 Run enable 1 source.
Selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (
11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
DIIL DIIL input (10.02 DI delayed status, bit 15). 30
Other [bit] Source selection (see Terms and abbreviations on page 148). -
No. Name/Value Description Def/FbEq16