No. Name/Value Description Def/FbEq16
Bit Name Information
0 Supply frequency
60 Hz
0 = 50 Hz; 1 = 60 Hz. Affects parameters 11.45, 11.59 , 12.20, 13.18,
30.11, 30.12, 30.13, 30.14, 31.26, 31.27, 40.15, 40.37, 41.15, 41.37,
46.01, 46.02.
1 Emergency stop
Cat 0
1 = Emergency stop, Category 0, without FSO module. Affects
21.04, 21.05, 23.11.
2 Emergency stop
Cat 1
1 = Emergency stop, Category 1, without FSO module. Affects
10.24, 21.04, 21.05, 23.11.
3 RO2 for -07
cabinet cooling fan
1 = Control of cabinet cooling fan (used only with specific
ACS880-07 hardware). Affects 10.27, 10.28, 10.29.
4 Externally powered
control unit
1 = Control unit powered externally. Affects 95.04. (Only visible with
a ZCU control unit)
5 DC supply switch 1 = DC switch monitoring active. Affects 20.12, 31.03, 95.08. (Only
visible with a ZCU control unit)
6 DOL motor switch 1 = Motor fan control active. Affects 10.24, 35.100, 35.103, 35.104.
7 xSFC-01 fuse
switch controller
1 = xSFC charging controller used. Affects 95.09. (Only visible with a
BCU control unit)
8 Service switch 1 = Service switch connected. Affects 31.01,
31.02.
9 Output contactor 1 = Output contactor present. Affects 10.24, 20.12.
10 Brake resistor, sine
filter, IP54 fan
1 = Status (eg. thermal) switches connected to DIIL input. Affects
20.11, 20.12.
11 INU-DSU
communication
1 = Diode supply unit control by inverter unit active. Makes several
parameters visible in groups 06, 60, 61, 62 and 94.
12 Reserved
13 du/dt filter
activation
1 = Active: An external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
Note: This bit is to be left at 0 if the drive/inverter module is
equipped with internal du/dt filtering (for example, frame R8i inverter
modules with option +E205).
14 DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-
line cooling fans (option +C188). Disables fan feedback monitoring
and changes fan control to ON/OFF type.
15 INU-ISU
communication
1 = IGBT supply unit control by inverter unit active. Makes several
parameters visible in groups 01, 05, 06, 07, 30, 31, 60, 61, 62, 94
and 96.