Parameters 195
Speed ref ramp in 23.01 Speed ref ramp input (page 257). 10
Speed ref ramped 23.02 Speed ref ramp output (page 257). 11
Speed ref used 24.01 Used speed reference (page 263). 12
Torq ref used 26.02 Torque reference used (page 279). 13
Freq ref used 28.02 Frequency ref ramp output (page 285). 14
Process PID out 40.01 Process PID output actual (page 341). 16
Process PID fbk 40.02 Process PID feedback actual (page 341). 17
Process PID act 40.03 Process PID setpoint actual (page 341). 18
Process PID dev 40.04 Process PID deviation actual (page 341). 19
Other Source selection (see Terms and abbreviations on page 148). -
11.58 Freq out 1 src min Defines the real value of the signal (selected by parameter
11.55 Freq out 1 source and shown by parameter 11.54 Freq
out 1 actual value) that corresponds to the minimum value of
frequency output 1 (defined by parameter 11.60 Freq out 1 at
src min).
0.000
-32768.000 …
32767.000
Real signal value corresponding to minimum value of
frequency output 1.
1 = 1
11.59 Freq out 1 src max Defines the real value of the signal (selected by parameter
11.55 Freq out 1 source and shown by parameter 11.54 Freq
out 1 actual value) that corresponds to the maximum value of
frequency output 1 (defined by parameter 11.61 Freq out 1 at
src max). See parameter 11.58 Freq out 1 src min.
1500.000;
1800.000
(95.20 b0)
-32768.000 …
32767.000
Real signal value corresponding to maximum value of
frequency output 1.
1 = 1
No. Name/Value Description Def/FbEq16
11.61
11.60
11.59 11.58
11.5911.58
11.61
11.60
Signal (real)
selected by
par. 11.5 5
Signal (real)
selected by
par. 11.5 5
f
out
(11.54 )
f
out
(11.54 )