EasyManua.ls Logo

ABB ACS880-104

ABB ACS880-104
664 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 189
Remote control Bit 9 of 06.11 Main status word (see page 166). 24
Supervision 1 Bit 0 of 32.01 Supervision status (see page 312). 33
Supervision 2 Bit 1 of 32.01 Supervision status (see page 312). 34
Supervision 3 Bit 2 of 32.01 Supervision status (see page 312). 35
RO/DIO control
word bit0
Bit 0 of 10.99 RO/DIO control word (see page 191). 40
RO/DIO control
word bit1
Bit 1 of 10.99 RO/DIO control word (see page 191). 41
RO/DIO control
word bit2
Bit 2 of 10.99 RO/DIO control word (see page 191). 42
RO/DIO control
word bit8
Bit 8 of 10.99 RO/DIO control word (see page 191). 43
RO/DIO control
word bit9
Bit 9 of 10.99 RO/DIO control word (see page 191). 44
Other [bit] Source selection (see Terms and abbreviations on page 148). -
10.25 RO1 ON delay Defines the activation delay for relay output RO1. 0.0 s
t
On
= 10.25 RO1 ON delay
t
Off
= 10.26 RO1 OFF delay
0.0 3000.0 s Activation delay for RO1. 10 = 1 s
10.26 RO1 OFF delay Defines the deactivation delay for relay output RO1. See
parameter 10.25 RO1 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for RO1. 10 = 1 s
10.27 RO2 source Selects a drive signal to be connected to relay output RO2.
For the available selections, see parameter 10.24 RO1
source.
Running
(95.20 b3)
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time

Table of Contents