352 Parameters
40.54 Set 1 trim mix When parameter 40.51 Set 1 trim mode is set to Combined,
defines the effect of direct and proportional trim sources in the
final trimming factor.
0.000 = 100% proportional
0.500 = 50% proportional, 50% direct
1.000 = 100% direct
0.000
0.000 … 1.000 Trim mix. 1 = 1
40.55 Set 1 trim adjust Defines a multiplier for the trimming factor. This value is
multiplied by the result of parameter 40.51 Set 1 trim mode.
Consequently, the result of the multiplication is used to
multiply the result of parameter 40.56 Set 1 trim source.
1.000
-100.000 …
100.000
Multiplier for trimming factor. 1 = 1
40.56 Set 1 trim source Selects the reference to be trimmed. PID ref
PID ref PID setpoint. 1
PID output PID controller output. 2
40.57 PID set1/set2
selection
Selects the source that determines whether process PID
parameter set 1 (parameters 40.0740.56) or set 2 (group
41 Process PID set 2) is used.
0 = Process PID parameter set 1 in use
1 = Process PID parameter set 2 in use
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 148). -
40.60 Set 1 PID activation
source
Selects a source that enables/disables process PID control.
See also parameter 40.07 Set 1 PID operation mode
.
0 = Process PID control disabled.
1 = Process PID control enabled.
On
Off 0. 0
On 1. 1
Follow Ext1/Ext2
selection
Process PID control is disabled when external control location
EXT1 is active, and enabled when external control location
EXT2 is active.
See also parameter 19.11 Ext1/Ext2 selection.
2
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 3
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 4
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 5
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 6
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 7
No. Name/Value Description Def/FbEq16