Fault tracing 597
7081 Control panel loss
Programmable fault: 49.05
Communication loss
action
Control panel (or PC tool) has
stopped communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Check the auxiliary code. The code
specifies the I/O port used as follows: 0:
Panel, 1: Fieldbus interface A, 2:
Fieldbus interface B, 3: Ethernet, 4:
D2D/EFB port).
7082 Ext I/O comm loss The I/O extension module
types specified by parameters
do not match the detected
configuration.
Check the auxiliary code (format
XXYY YYYY). “XX” specifies the number
of the I/O extension module (01:
parameter group 14 I/O extension
module 1, 02: 15 I/O extension module 2,
03: 16 I/O extension module 3).
“YY YYYY” indicates the problem (see
actions for each code below).
00 0001 Communication with module
failed.
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
00 0002 Module not found. Check the type and location settings of
the modules (parameters 14.01/14.02,
15.01/15.02 or 16.01/16.02).
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
00 0003 Configuration of module failed.
00 0004 Configuration of module failed.
7083 Panel reference
conflict
Use of saved control panel
reference in multiple control
modes attempted.
The control panel reference can only be
saved for one reference type at a time.
Consider the possibility of using a copied
reference instead of saved reference
(see the reference selection parameter).
7084 Panel/PC tool version
conflict
The current version of the
control panel and/or PC tool
does not support a function.
(For example, older panel
versions cannot be used as a
source of external reference.)
Update control panel and/or PC tool.
Contact your local ABB representative if
necessary.
7085 Incompatible option
module
Option module not supported.
(For example, type Fxxx-xx-M
fieldbus adapter modules are
not supported.)
Check the auxiliary code. The code
specifies the interface to which the
unsupported module is connected:
1: Fieldbus interface A,
2: Fieldbus
interface B.
Replace the module with a supported
type.
7121 Motor stall
Programmable fault: 31.24
Stall function
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Check motor load and drive ratings.
Check fault function parameters.
Code
(hex)
Fault Cause What to do