406 Parameters
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7 Single output X113:7
DO X113:8 Single output X113:8
DO X113:9 Single output X113:9
DO X114:7 Single output X114:7
DO X114:8 Single output X114:8
DO X114:9 Single output X114:9
FSOGEN.21 Motor nominal
speed
Sets the nominal motor speed. 100.0 rpm
1.0 …35880.0 rpm Speed
FSOGEN.22 Motor nominal
frequency
Sets the nominal motor frequency.
Note: For a DCS880 drive, this value must
be set to 25 Hz.
1.00 Hz
1.00…598.00 Hz Frequency
FSOGEN.31 Transient mute time Sets the mute time for the safe speed
functions. The FSO module waits for the
transient mute time before it acts after a
ramp monitoring or trip limit hit, or after the
zero speed limit is reached.
W
hen an encoder is used: This parameter is
used only in ramp monitoring and trip limit hit
situations.
0ms
0…1000 ms Time
FSOGEN.32 Zero speed delay
time
Sets the time for how long the motor speed
must stay inside zero speed limits in order to
determine the motor as stopped.
Note: This parameter is relevant only when
an encoder is used. Without an encoder,
parameter FSOGEN.31 is used. See also
section Configuring mute times on
page 393.
0ms
0…1000 ms Time
FSOGEN.33 Monitoring start
delay
Sets the time for how long the speed must
stay in the correct side of a limit in order to
determine that the limit is reached and
monitoring can be started.
Note: This parameter is relevant only when
an encoder is used. Without an encoder,
parameter FSOGEN.31 is used. See also
section Configuring mute times on
page 393.
0ms
0…1000 ms Time