Parameters 407
FSOGEN.38 Enable SLSx mute
times
Enables SLS-specific mute times which are
used in SLS limit hit situations.
These mute times can be set with
parameters SLSx.17, SLSx.27, SLSx.37,
SLSx.47 and SLSx.57. These parameters
are effective only with the safe speed
estimate.
When this parameter is disabled,
FSOGEN.31 is used in limit hit situations.
Disabled
Disabled Deactivates SLSx mute times
Enabled Activates SLSx mute times
FSOGEN.39 Enable SMS mute
time
Enables SMS-specific mute time, which is
used in limit hit situations and can be set
with parameter SMS.17. This parameter is
effective only with the safe speed estimate.
When this parameter is disabled,
FSOGEN.31 is used in limit hit situations.
Disabled
Disabled Deactivates SMS mute time
Enabled Activates SMS mute time
FSOGEN.41 Power-up
acknowledgement
Sets the power-up acknowledgement
method.
Note: If a safety function request is active
when the FSO module is rebooted, the
request must be removed before the power-
up acknowledgement is accepted.
Manual
Manual The FSO module reads an external
acknowledgement signal through the digital
input defined by parameter FSOGEN.42
Acknowledgement button input.
Automatic The FSO module generates the
acknowledgement signal automatically after
the power-up.
Safebus The FSO module expects an external
acknowledgement signal from the safety
fieldbus after the power-up.
Manual_Safebus The FSO module expects an external
acknowledgement signal either from a digital
input or from the safety fieldbus after the
power-up.
FSOGEN.42 Acknowledgement
button input
Sets the digital input that is connected to the
button for acknowledgement operations.
None
None No input connected
DI X113:1 Single input X113:1
DI X113:2 Single input X113:2