426 Parameters
SLSx.16 SLS1 output B Sets the secondary digital output for the
SLS1 function. Active when SLS1 function is
active and the motor speed is below the
SLS1 limit (that is, when the SLS1
monitoring is on).
The secondary output is mostly used for
cascade connection.
See parameters SAFEIO.12 Cascade A and
SAFEIO.13 Cascade B.
None
None No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7 Single output X113:7
DO X113:8 Single output X113:8
DO X113:9 Single output X113:9
DO X114:7 Single output X114:7
DO X114:8 Single output X114:8
DO X114:9 Single output X114:9
SLSx.17 Mute time for SLS1 Sets the SLS1 specific mute time for limit hit
situations.
This parameter is effective only with the safe
speed estimate.
0 ms
0…10000 ms
SLSx.21 SLS2 input Sets the digital input for the SLS2 function. None
None No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1 Single input X113:1
DI X113:2 Single input X113:2
DI X113:3 Single input X113:3
DI X113:4 Single input X113:4
DI X114:1 Single input X114:1
DI X114:2 Single input X114:2
DI X114:3 Single input X114:3
DI X114:4 Single input X114:4
SLSx.22 SLS2 trip limit
negative
Sets the SLS2 negative speed limit that trips
the drive.
0.0 rpm
-35880.0 …0.0 rpm Speed
Index Name/Value Description Factory
default

Table of Contents