Parameters 417
POUS.22 POUS completed
output
Set the digital output that indicates the
completion of the POUS function. Active
after the time defined by parameter
POUS.13 POUS delay for completion has
elapsed from the POUS request until the
POUS request has been removed.
Note: Connect the POUS indication lamp to
this output.
None
None No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7 Single output X113:7
DO X113:8 Single output X113:8
DO X113:9 Single output X113:9
DO X114:7 Single output X114:7
DO X114:8 Single output X114:8
DO X114:9 Single output X114:9
41
SSE
Parameters for the SSE function
SSE.01 SSE version Shows the version of the SSE function. Version 1
Version 1 Version 1.
SSE.11 SSE input A Sets the digital input that is connected to the
primary input of the SSE function.
None
None No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1 Single input X113:1
DI X113:2 Single input X113:2
DI X113:3 Single input X113:3
DI X113:4 Single input X113:4
DI X114:1 Single input X114:1
DI X114:2 Single input X114:2
DI X114:3 Single input X114:3
DI X114:4 Single input X114:4