418 Parameters
SSE.12 SSE input B Sets the digital input that is connected to the
secondary input of the SSE function. The
secondary input is mostly used for the
cascade connection.
See parameters SAFEIO.12 Cascade A and
SAFEIO.13 Cascade B.
None
None No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1 Single input X113:1
DI X113:2 Single input X113:2
DI X113:3 Single input X113:3
DI X113:4 Single input X113:4
DI X114:1 Single input X114:1
DI X114:2 Single input X114:2
DI X114:3 Single input X114:3
DI X114:4 Single input X114:4
SSE.13 SSE function Sets the type of the SSE function. Emergency
ramp
Immediate STO The FSO module activates the drive STO
immediately after the SSE request.
Emergency ramp The FSO module activates the drive STO
after an emergency ramp.
SSE.14 SSE monitoring
method
Sets the method used for the SSE
emergency ramp monitoring. This parameter
is relevant only if parameter SSE.13 SSE
function is set to Emergency ramp.
Ramp
Ramp Ramp monitoring. SAR0 parameters define
the emergency ramp and monitoring limits.
See parameters 200.102, SARx.11,
SARx.12 and SARx.02.
Time Time monitoring. Parameter 200.102 SAR0
ramp time to zero defines the emergency
ramp and it is monitored with parameter
SSE.15 SSE delay for STO.
SSE.15 SSE delay for STO Sets the delay for STO activation after the
SSE request.
This parameter is relevant only if parameter
SSE.13 SSE function is set to Emergency
ramp, time monitoring is used (SSE.14 SSE
monitoring method = Time) and the motor
speed does not follow the ramp.
3,600,000
ms
Index Name/Value Description Factory
default