DefaultDescriptionName/ValueNo.
N/ARead-only. Displays major and minor revision numbers
of the adapter module's firmware version in xxyy
format, where:
FBA A/B appl SW ver33
xx = major revision number
yy = minor revision number
Example: If the firmware version (<ma-
jor>.<minor>.<patch>.<build>) is 3.10.200.13 or
3.10.0.0, the value 310 is displayed.
See also parameter 32.
FSPS-21 configuration parameters group B (group 2)
Note: The actual parameter group number depends on the drive type. Group B (group 2)
corresponds to:
parameter group 53 in ACS380 and ACS580
parameter group 53 in ACS880 if the adapter is installed as fieldbus adapter A or group
56 if the adapter is installed as fieldbus adapter B.
DefaultDescriptionName/ValueNo.
1 or 11
1)
Selects the resolution of control word (16 bit or 32 bit)
received by the drive.
FBA data out 1 (mas-
ter to drive)
01
Control word (16 bits)1 = CW 16bit
Control word (32 bits)11 = CW 32bit
0 or 2Selects data word 1 received by the drive over the
PROFINET network. The content is defined by a
decimal number in the range of 0 to 9999 as follows:
FBA data out 202
Not used0
Virtual address area of drive control1...99
Parameter area of the drive101...
9999
Not used0 = None
Control word (16 bits)1 = CW 16bit
Reference REF1 (16 bits)2 = Ref1 16bit
Reference REF2 (16 bits)3 = Ref2 16bit
Control word (32 bits)11 = CW 32bit
Reference REF1(32 bits)12 = Ref1 32bit
Reference REF2 (32 bits)13 = Ref2 32bit
Control word 2 (16 bits)21 = CW2 16bit
Parameter index with format xxyy, where101…9999
xx is the parameter group number (1…99)
yy is the parameter number index within that group
(01…99).
Path to parameter area selection.Other
54 PROFINET IO Start-up