tables below and must be checked first and adjusted where necessary. You can adjust the
parameters via a drive control panel or a PC tool.
• The new parameter settings take effect only when you power up the module the next
time or when you activate the fieldbus adapter refresh parameter.
FSPS-21 configuration parameters – group A (group 1)
Note:
The actual parameter group number depends on the drive type. Group A (group 1)
corresponds to:
• parameter group 51 in ACS380 and ACS580.
• parameter group 51 in ACS880 if the adapter is installed as fieldbus adapter A or group
54 if the adapter is installed as fieldbus adapter B.
DefaultDescriptionName/ValueNo.
133 = PROFIsafeRead-only. Shows the fieldbus adapter type as detec-
ted by the drive. The value cannot be adjusted by the
user.
If the value is 0 = None, the communication between
the drive and the module has not been established.
FBA type01
11 = PNIO ABB ProSelects the application protocol and communication
profile for the network connection.
The selections available for PROFINET IO communic-
ation are listed below.
Protocol.Profile02
PROFINET IO protocol: PROFIdrive profile10 = PNIO Pdrive
PROFINET IO protocol: ABB Drives profile11 = PNIO ABB Pro
PROFINET IO protocol: Transparent 16-bit profile12 = PNIO T16
PROFINET IO protocol: Transparent 32-bit profile13 = PNIO T32
PROFINET IO protocol: PROFIdrive positioning mode14 = PNIO PdriveM
0 = AutoSets the bit rate for the Ethernet interface.Commrate03
Auto-negotiate0 = Auto
100 Mbps, full duplex1 = 100 Mbps FD
100 Mbps, half duplex2 = 100 Mbps HD
10 Mbps, full duplex3 = 10 Mbps FD
10 Mbps, half duplex4 = 10 Mbps HD