DescriptionData typeR/W
1)
Par. no.
Subnet mask of stationUnsigned32R61004
1)
Read and/or Write
2)
The meaning of vendor-specific bits is defined by the drive control program.
3)
Support depends on the drive type.
I&M records
I&M (Identification & Maintenance) records can be read, for example, with the DTM tool.
The FSPS-21 module supports the mandatory I&M0 record as well as the optional I&M1,
I&M2, I&M3 and I&M4 records.
Call-REQ-PDU telegram for read/write access to I&M records
Record Data IndexFunction
0xAFF0I&M0
0xAFF1I&M1
0xAFF2I&M2
0xAFF3I&M3
0xAFF4I&M4
Response structure for I&M0 (Read-only)
CodingSizeContents
10 OctetsHeader
0x1A = ABB Automation2 OctetsMANUFACTURER_IDI&M block
6438177508335 = EAN code for
FSPS-21 kit
20 OctetsORDER_ID
Serial number of FSPS-21 module16 OctetsSERIAL_NUMBER
Hardware version of FSPS-21 module2 OctetsHARDWARE_REVISION
Format: V255.255.255 E.g., V1.0.0 =
software version 100
4 OctetsSOFTWARE_REVISION
(Marks a change of hardware or its
parameters)
2 OctetsREVISION_COUNTER
3A00 (…3AFF) PROFIdrive2 OctetsPROFILE_ID
0 = no specific type2 OctetsPROFILE_SPECIFIC_ TYPE
0x0101 = version 1.12 OctetsIM_VERSION
30 = I&M0, I&M1, I&M2, I&M3 and
I&M4 supported
2 OctetsIM_SUPPORTED
206 Appendix A PROFIdrive parameters and I&M records of PROFINET IO