Control elements and application parameter
Application "Fault and alarm messages" - Settings of the individual messages
Product manual 2CKA001473B5023
119
2.16 Application "Fault and alarm messages" - Settings of the individual messages
2.16.1 Name of message
Options: <Name>
Designation of message. The length of the name is limited to 60 characters.
2.16.2 Type of message
Options: Alarm
Notice
Error
The parameter is used to specify the type of message that is displayed.
2.16.3 Type of alarm
Options: 1 bit
14 bytes
The parameter is used to specify whether the alarm is displayed and sent with or without text.
– 1 bit: No text is displayed and sent when acknowledging the alarm. The following
supplementary parameters are available:
Text for alarm message:
Options: <Text>
The parameter is used to specify the text that is displayed when this message appears. The
length of the text is limited to 60 characters.
Sending 0 at acknowledgement:
Options: Deactivated
Activated
The parameter is used to specify whether "0" is sent at acknowledgement.
Acoustic alarm signal:
Options: Deactivated
Activated
The parameter is used to specify whether the signal tone specified under the global settings
is played .
– Deactivated: No acoustic alarm signal. No additional parameters available.
– Activated: The signal tone is played at an alarm signal. The following supplementary
parameter is available:
Duration of audio signal [min.]:
Options: Setting option from 1 - 60
The parameter is used to specify how long the specified signal tone is to be played (in
minutes).