Control elements and application parameter
"Dimmer" control element
Product manual 2CKA001473B5023
62
2.3.10 Manner of dimming
Options: Start/stop
Stepwise
Value
– Start/stop: When the button is pressed a telegram with the information "dim brighter" or "dim
darker" is sent. When the button is released a telegram with the information "top dimming" is
sent.
Long operation after ...:
Options: Setting option from 0.3 - 10 seconds
The parameter is used to specify how long the button must be pressed to recognize a long
operation.
– Stepwise: The following parameters are displayed:
Long operation after ...:
Options: Setting option from 0.3 - 10 seconds
The parameter is used to specify how long the button must be pressed to recognize a long
operation.
Brightness change [%]:
Options: Setting option in % (different values)
The parameter is used to specify in which step widths to dim.
Telegram is repeated every [sec.]:
Options: Setting option from 0.25 - 1.25 seconds
The parameter is used to specify the space of time between two dimming telegrams.
– Value: The following parameters are displayed:
Long operation after ...:
Options: Setting option from 0.3 - 10 seconds
The parameter is used to specify how long the button must be pressed to recognize a long
operation.
Brightness change [%]:
Options: Setting option in % from 1 - 20
The parameter is used to specify in how many stepless steps dimming takes place.
Telegram is repeated every [sec.]:
Options: Setting option from 0.25 - 1.25 seconds
The parameter is used to specify the space of time between two dimming telegrams.
2.3.11 Enable 1-bit communication object "Disable"