Control elements and application parameter
Application "Internal RTC"
Product manual 2CKA001473B5023
172
2.21.97 Summer compensation — Offset of the set-point temperature for the exit from summer
compensation (x 0.1°C)
Options: Setting option between -127 - 127
The parameter is used to define how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the upper temperature value is reached.
Typical values for summer compensation are:
■
20°C: Lower outside temperature value
■
32°C: Upper outside temperature value
■
0 K: Lower setpoint offset
■
4 K: Upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Note
This parameter is only available if the "Summer compensation" parameter is set
to "Yes".
Note
The following parameters are available when the "Controller function" parameter
is set on "Cooling with additional stage".
The same parameters are available which are also available when parameter
"Controller function" is set on "Cooling" and parameter "Control value type" on
"2-point 1 bit, On/Off" or "2-point 1 byte, 0/100%".
Note
The additional parameter "Control value type" is available for the additional step.