2.10.7 Type of display element — Value display — Object type
Options: 1-byte value [0% - 100%]
1-byte value [0 - 255]
1-byte value [-128 - 127]
2-byte value [0 - 65535]
2-byte value [-32768 - +32767]
2-byte floating point
4-byte value [0 - 4294967295]
4-byte value [-2147483648 - 2147483647]
4-byte floating point
14-byte text
Parameter "Object type" is used to specify the size of the communication object.
1-byte value [0% - 100%]: A value is sent as 1-byte value without a sign (percentage value).
1-byte value [0 - 255]: A value is sent as 1-byte value without a sign, e.g. actuating value,
angle or brightness value.
1-byte value [-128 - 127]: A value is sent as 1-byte value with a sign, e.g. actuating value.
2-byte value [0 - 65535]: A value is sent as 2-byte value without a sign, e.g. actuating value
or time interval.
2-byte value [-32768 - +32767]: A value is sent as 2-byte value with a sign, e.g. actuating
value or time difference.
2-byte floating point: A value is sent as 2-byte floating point value, e.g. a temperature value,
a time duration, a performance or a consumption value.
4-byte value [0 - 4294967295]: A value is sent as 4-byte value without a sign, e.g. actuating
value.
4-byte value [-2147483648 - 2147483647]: A value is sent as 4-byte value with a sign, e.g.
actuating value or time difference.
4-byte floating point: A value is sent as 4-byte floating point value, e.g. an energy display,
electric current (A), electric power (W), DTP 14.
14-byte value: Makes it possible to send any text with a maximum of 14 characters.
The following supplementary parameters are available for all options, except for option "14-byte
value":
Notice
Different values can be preset or set, depending on the selected option.
Unit:
Options: <Text>
The parameter is used to enter the unit or the unit sign with which the value is displayed in the
display element.
The length of the text is limited to 60 characters.