Commissioning of the KNX Function via DCA (from ETS5)
Product manual 2CKA001473B5023
25
Temperature
Notice
The temperature parameters refer to the temperature display in the bottom
bar of the display.
In the "Basic KNX settings" it can be specified directly in the device that the
temperature values are displayed in the bottom bar of the panel.
■
Use for room temperature sensor
Options: Indoor sensor
Outdoor sensor
The parameter is used to specify whether the room temperature is measured via the indoor
sensor of the device or via an outdoor KNX temperature sensor.
The outdoor sensor must be allocated via a group address.
■
Offset for temperature measurement [K]
Options: Setting option from -12.8 - +12.7 K
The parameter is used to specify the display of the temperature in units of °C (Celsius) or °F
(Fahrenheit).
■
Send indoor sensor temperature
Options: Do not send
During change
Cyclic
During change and cyclic
The parameter is used to specify whether or when the temperature values of the indoor
sensor are passed on to other devices.
■
Cycle time for automatic transmission of the internal sensor temperature [sec.]
Options: Setting option from 5 - 3600 seconds
The parameter is used to specify the intervals at which the temperature values of the indoor
sensor are passed on to other devices.