165
1SFC132003M0201
7URXEOHVKRRWLQJ
&KDSWHU
8QGHUORDGSURWHFWLRQ The motor current is below set
level and time.
Check and correct the reason for the
underload.
Check that the settings are according to
the operation conditions.
/RFNHGURWRUSURWHFWLRQ The motor is running stiff by
some reason.
A damaged bearing or a stucked
load could be possible causes.
Check the bearings of the motor and
load.
Check that the load is not running stiff.
+LJKFXUUHQWSURWHFWLRQ A fault current, higher than 8
times the softstarter ratings, has
occurred.
Check the circuits including the motor for
any insulation fault phase to phase or
earth fault.
3KDVHLPEDODQFHSURWHFWLRQ Unbalance in the phase currents. Check the main voltage and the motor
circuit.
Restart the motor and check the phase
currents
3KDVHUHYHUVDOSURWHFWLRQ The phase sequence is not
correct.
Change the phase sequence on the line
side to (L1-L2-L3).
6WDWXV 3RVVLEOHFDXVH 6ROXWLRQ
Power on ProtectionFault
2TQV7PFGTNQCF
4GUGV $CEM
Power on ProtectionFault
2TQV.QEMGF4QV
4GUGV $CEM
Power on ProtectionFault
2TQV*KIJ+
4GUGV $CEM
Power on ProtectionFault
2TQV2JCUG+OD
4GUGV $CEM
Power on ProtectionFault
2TQV2JCUG4GX
4GUGV $CEM