ABB RER670 - Settings for Step 1

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
U
ref
I
dir
IEC09000636_2_vsd
1
2
2
3
4
IEC09000636 V2 EN-US
Figure 50: Directional function characteristic
1. RCA = Relay characteristic angle
2. ROA = Relay operating angle
3. Reverse
4. Forward
8.2.3.1 Settings for step 1
M12982-19 v10
Operation1: This is used to Off/On the operation of step 1.
StartCurr1: This is used to set operate current level for step 1 given in % of IBase.
CurveType1: Selection of time characteristic for step 1. Definite time delay and
different types of inverse time characteristics are available according to Table
19.
Section 8 1MRK 506 375-UEN A
Current protection
164 Railway application RER670 2.2 IEC
Application manual