Figure 50: Directional function characteristic
1. RCA = Relay characteristic angle
2. ROA = Relay operating angle
3. Reverse
4. Forward
8.2.3.1 Settings for step 1
M12982-19 v10
Operation1: This is used to Off/On the operation of step 1.
StartCurr1: This is used to set operate current level for step 1 given in % of IBase.
CurveType1: Selection of time characteristic for step 1. Definite time delay and
different types of inverse time characteristics are available according to Table
19.
Section 8 1MRK 506 375-UEN A
Current protection
164 Railway application RER670 2.2 IEC
Application manual