LONChannelMask
or
SPAChannelMask
M12811-15 v2
Definition of which part of the event function block that shall generate events:
Off
Channel 1-8
Channel 9-16
Channel 1-16
MinRepIntVal
(1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input
channel. This can be set between 0 s to 3600 s in steps of 1 s. It should normally be
set to 0, that is, no cyclic communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an
optimized way to minimize the load on the station bus.
15.6 Disturbance report DRPRDRE
IP14584-1 v2
15.6.1 Identification
M16055-1 v8
Function description IEC 61850 identification IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A4RADR - -
Disturbance report B1RBDR - B22RBDR - -
15.6.2 Application
M12152-3 v9
To get fast, complete and reliable information about disturbances in the primary
and/or in the secondary system it is very important to gather information on fault
currents, voltages and events. It is also important having a continuous event-
logging to be able to monitor in an overview perspective. These tasks are
accomplished by the disturbance report function DRPRDRE and facilitate a better
understanding of the power system behavior and related primary and secondary
equipment during and after a disturbance. An analysis of the recorded data
provides valuable information that can be used to explain a disturbance, basis for
change of IED setting plan, improve existing equipment, and so on. This
information can also be used in a longer perspective when planning for and
designing new installations, that is, a disturbance recording could be a part of
Functional Analysis (FA).