14.1.2.4 Blocking of the function block
M14828-21 v4
Total block of the trip function is done by activating the input BLOCK and can be
used to disable the outputs of the trip logic in the event of internal failures.
14.1.3 Setting guidelines
M12274-3 v8
The parameters for tripping logic SMPPTRC are set via the local HMI or PCM600.
The following trip parameters can be set to regulate tripping.
Operation
: Sets the mode of operation. Off switches the tripping off. The normal
selection is On.
TripLockout: Sets the scheme for lockout. Off only activates the lockout output
when the input SETLKOUT is activated. On activates the lockout output and
latches the output TRIP when the input SETLKOUT is activated. The normal
selection is Off.
AutoLock: Sets the scheme for lockout. Off only activates lockout through the input
SETLKOUT. On additionally allows activation of lockout from the trip function
itself. The normal selection is Off.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set to
ensure that the circuit breaker is tripped correctly. Normal setting is 0.150s.
14.2 Trip matrix logic TMAGAPC
IP15121-1 v4
14.2.1 Identification
SEMOD167882-2 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic TMAGAPC - -
14.2.2 Application
M15321-3 v12
The trip matrix logic TMAGAPC function is used to route trip signals and other
logical output signals to different output contacts on the IED.
The trip matrix logic function has 3 output signals and these outputs can be
connected to physical tripping outputs according to the specific application needs
for settable pulse or steady output.