The setting parameters are:
LineLength1
Set with length of section 1 in km
RL1
Set with positive sequence resistance of section 1 per phase
XL1
Set with positive sequence reactance of section 1 per phase
REOverRL1
Set with ratio of RE by RL of section 1, this can be derived from positive and
zero sequences impedances as:
IECEQUATION15082 V1 EN-US
Where
R01
is zero sequence resistance of section 1 per phase.
XEOverXL1
Set with ratio of XE by XL of section 1, this can be derived from positive and zero
sequences impedances as:
IECEQUATION15083 V1 EN-US
Where
X01
is zero sequence reactance of section 1 per phase.
The settings are set in the same way for line sections 2, 3 and so on.
15.10.3.1 Setting example
GUID-F3F5D7EC-1574-45F1-8D54-632D6E66D960 v2
Consider a 1
10kV/16.7Hz system with three transmission line sections (see Figure
167).
Source A
1 2 3
RFLO
Source B
IEC15000299-1-en.vsdx
IEC15000299 V1 EN-US
Figure 167: Single line diagram with three line sections
RWRFLO function should set for the NrOfSections. Since number of transmission
line sections is three, the NrOfSections should also be set to three (3). Table
41
provides the system line specifications for three transmission lines.