14.4 Logic for group alarm WRNCALH
14.4.1 Identification
GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group warning WRNCALH - -
14.4.1.1 Application
GUID-FC0DBB7B-FF86-44BF-83D6-DDF120A176DE v1
Group warning logic function WRNCALH is used to route warning signals to
LEDs and/or output contacts on the IED.
WRNCALH output signal W
ARNING and the physical outputs allows the user to
adapt the warning signal to physical tripping outputs according to the specific
application needs.
14.4.1.2
Setting guidelines
GUID-B08F2636-33DA-4937-92EB-1A8AC0909AB4 v2
OperationOn or Off
14.5 Logic for group indication INDCALH
14.5.1 Identification
GUID-3B5D4371-420D-4249-B6A4-5A168920D635 v4
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group indication INDCALH - -
14.5.1.1 Application
GUID-9BAD30FB-4B75-4E14-82A8-6A59B09FA6EA v1
Group indication logic function INDCALH is used to route indication signals to
different LEDs and/or output contacts on the IED.
INDCALH output signal IND and the physical outputs allows the user to adapt the
indication signal to physical outputs according to the specific application needs.
14.5.1.2 Setting guidelines
GUID-7E776D39-1A42-4F90-BF50-9B38F494A01E v2
Operation
: On or Off
Section 14 1MRK 506 375-UEN A
Logic
364 Railway application RER670 2.2 IEC
Application manual