PresLOLimit: This is used to set the limit for a pressure lockout condition in the
circuit breaker.
T
empAlarmLimit: This is used to set the limit for a temperature alarm condition in
the circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in
the circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication,
given in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout
indication, given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set
time delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set
time delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a
set time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.
15.3 Liquid medium supervision SSIML
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
15.3.1 Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function SSIML - 71
15.3.2 Application
GUID-140AA10C-4E93-4C23-AD57-895FADB0DB29 v6
Liquid medium supervision (SSIML) is used for monitoring the transformers and
tap changers. When the level becomes too low compared to the required value, the
operation is blocked to minimize the risk of internal failures. Binary information
based on the oil level in the transformer and the tap changer is used as input signals
1MRK 506 375-UEN A Section 15
Monitoring
Railway application RER670 2.2 IEC 389
Application manual