Figure 73: Example of I/O-signal connections at an auto reclosing sequence
12.2.3.2 Auto recloser settings
GUID-74980A07-CF89-488F-AB17-E5351D0032EE v1
The settings for the auto recloser are set using the local HMI (LHMI) or PCM600.
This setting guideline describes the settings of the auto recloser using the LHMI.
The settings for the auto recloser are found under Main menu/Settings/IED
Settings/Control/AutoRecloser(79,5(0->1))/SMBRREC(79,5(0->)):X and have
been divided into four different setting groups: General, CircuitBreaker, DeadTime
and MasterSlave.
General settings
Operation: The operation of the auto recloser can be switched On or Off.
ExternalCtrl: This setting makes it possible to switch the auto recloser On or Off
using an external switch via IO or communication ports.
StartByCBOpen: The normal setting Off is used when the function is started by
protection trip signals. If set On the start of the auto recloser is controlled by an
circuit breaker auxiliary contact.
LongStartInhib: Usually the protection trip command, used as an auto reclosing
start signal, resets quickly as the fault is cleared. A prolonged trip command may