EasyManua.ls Logo

ABB RER670 - Configuration Setting; Signals from Bus-Coupler

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.4.4.2 Signals from bus-coupler
M13566-6 v4
If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-
busbar connection could exist via the bus-section disconnector and bus-coupler
within the other bus-section.
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO ABC_BCAB_TRAFO ABC_BC
(WA1)A1
(WA2)B1
(WA7)C C
B2
A2
en04000487.vsd
IEC04000487 V1 EN-US
Figure 95: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic for input signals concerning bus-coupler are the same as
the specific logic for the line bay (ABC_LINE):
Signal
BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12 The switch status of BC_12 is valid.
EXDU_BC No transmission error from bus-coupler bay (BC).
The logic is identical to the double busbar configuration “Signals from bus-
coupler“.
12.4.4.3
Configuration setting
M13566-22 v5
If there are no second busbar B and therefore no QB2 disconnector, then the
interlocking for QB2 is not used. The state for QB2, QC21, BC_12 are set to open
by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
QB2_OP = 1
QB2QB2_CL = 0
QC21_OP = 1
QC21_CL = 0
BC_12_CL = 0
VP_BC_12 = 1
1MRK 506 375-UEN A Section 12
Control
Railway application RER670 2.2 IEC 267
Application manual

Table of Contents

Other manuals for ABB RER670

Related product manuals