The restricted earth fault protection is not affected, as a differential protection, with
the following power transformer related phenomena:
magnetizing inrush currents
overexcitation magnetizing currents
load tap changer
external and internal phase faults which do not involve earth
symmetrical overload conditions
Due to its features, REFPDIF is often used as a main protection of the transformer
winding for all faults involving earth.
6.1.2.1 Transformer winding, solidly earthed
M13048-3 v10
The most common application is on a solidly earthed transformer winding. The
connection is shown in Figure
29.
IEC16000117-1-en.vsdx
REFPDIF
I2P
ISI
IdN/I
Protected
winding
IEC16000117 V1 EN-US
Figure 29: Connection of the low impedance Restricted earth fault function
REFPDIF for a directly (solidly) earthed transformer winding
Section 6 1MRK 506 375-UEN A
Differential protection
76 Railway application RER670 2.2 IEC