Table 40: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation
Operation
Off
/
On On
Function must be
On
k Low pass filter coefficient for
power measurement, U and I
0.00 Typically no additional filtering is
required
UGenZeroDb Zero point clamping in % of
Ubase
25 Set minimum voltage level to
25%
IGenZeroDb Zero point clamping in % of
Ibase
3 Set minimum current level to 3%
UBase (set in
Global base)
Base setting for voltage level in
kV
15.00 Set LV side rated phase-to-
phase voltage
IBase (set in
Global base)
Base setting for current level in
A
533A Set transformer LV winding rated
current
SBase (set in
Global base)
Base setting for power level in
MVA
8 Set rated apparent power of the
transformer
15.2 Gas medium supervision SSIMG
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
15.2.1 Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function SSIMG - 63
15.2.2 Application
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
Gas medium supervision (SSIMG) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the
circuit breaker operation shall be blocked to minimize the risk of internal failure.
Binary information based on the gas pressure in the circuit breaker is used as an
input signal to the function. The function generates alarms based on the received
information.
15.2.3 Setting guidelines
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v2
The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation
: This is used to disable/enable the operation of gas medium supervision
i.e. Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the
circuit breaker.