IEC05000462 V2 EN-US
Figure 10: Example how to set CTStarPoint parameters in the IED
4.2.2.4 Examples on how to connect, configure and set CT inputs for most
commonly used CT connections
SEMOD55055-296 v7
Figure
11 defines the marking of current transformer terminals commonly used
around the world:
In the SMAI function block, you have to set if the SMAI block is
measuring current or voltage. This is done with the parameter:
AnalogInputType: Current/V
oltage. The ConnectionType: phase -
phase/phase-earth and GlobalBaseSel.
Section 4 1MRK 506 375-UEN A
Analog inputs
48 Railway application RER670 2.2 IEC
Application manual