it is a useful function in circuits for local or remote automation processes in the
power system.
9.1.3 Setting guidelines
M13851-3 v9
All the voltage conditions in the system where U2R
WPTUV performs its functions
should be considered. The same also applies to the associated equipment, its
voltage and time characteristic.
There are wide applications where general undervoltage functions are used. All
voltage related settings are made as a percentage of the global base value UBase
and base current IBase, which normally is set to the primary rated voltage level
(phase-to-phase) of the power system or the high voltage equipment under
consideration.
The setting for U2RWPTUV is normally not critical, since there must be enough
time available for the main protection to clear short circuits and earth faults.
Some applications and related setting guidelines for the voltage level are described
in the following sections.
9.1.3.1 Disconnected equipment detection
M13851-53 v3
The setting must be below the lowest occurring "normal" voltage and above the
highest occurring voltage, caused by inductive or capacitive coupling, when the
equipment is disconnected.
9.1.3.2 Power supply quality
M13851-56 v3
The setting must be below the lowest occurring "normal" voltage and above the
lowest acceptable voltage, due to regulation, good practice or other agreements.
9.1.3.3 Voltage instability mitigation
M13851-59 v3
This setting is very much dependent on the power system characteristics, and
thorough studies have to be made to find the suitable levels.
9.1.3.4 Backup protection for power system faults
M13851-62 v3
The setting must be below the lowest occurring "normal" voltage and above the
highest occurring voltage during the fault conditions under consideration.
9.1.3.5 Settings for two step undervoltage protection
M13851-65 v14
Parameters for U2RWPTUV application function are set via local HMI or
Protection and Control Manager PCM600.
Section 9 1MRK 506 375-UEN A
Voltage protection
196 Railway application RER670 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RER670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RER670 and is the answer not in the manual?

ABB RER670 Specifications

General IconGeneral
TypeProtection Relay
Product TypeRER670
Current Input1 A / 5 A
DisplayLCD
Voltage Rating1000 V
Communication ProtocolsIEC 61850, Modbus
Protection FunctionsOvercurrent, Earth Fault, Differential
MountingPanel
HousingMetal

Related product manuals