ABB RER670 - Setting Examples; Compensated Earthed Systems

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timers
separated
, Timers linked, General start, PhSel start, Internal start and External
start. The default setting is Timers separated.
OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer
of zone 6. The default setting is Off.
tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6.
It should be set to 0.0 s.
OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer
of zone 6. The default setting is Off.
tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6.
It should be set to 0.0 s.
Phase Selection
GUID-62310709-49F4-4D60-869C-2145D574B459 v2
tI0: Delay time for the residual overcurrent start. Residual overcurrent start is
delayed by settable time delay tI0. The default setting is 0.2s.
ModeU0DetMin: This is used to enable/disable the neutral voltage shift protection.
The default setting is Off.
U0DetMin: This is used to set the minimum operate value for the neutral voltage
shift. The default value is 20% UB.
UDisp
GUID-1885B794-9F95-446B-A656-0A37AAB7F193 v2
OpModeU0: This is used for the Off/On operation of the neutral voltage
displacement logic. The default value is Off.
UMinDisp: This is used to check the neutral voltage displacement for single phase-
earth-faults occur in the system. The default setting is 150% UB.
tU0: This is the time delay to trip for the neutral voltage displacement start. The
default value is 5.0s.
7.2.3 Setting examples
7.2.3.1 Compensated earthed systems
GUID-C9010253-2D63-485B-ACF9-48166C03E017 v2
Example in Figure
42 illustrates how the distance protection ZRWPDIS protects a
1
10kV overhead transmission line. The earthing considered is compensated earthed
system.
Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 are
considered in this example. Zones 4, 5 and 6 can be set on similar lines depending
on the application they are being used.
All the settings for impedance are in Ohms Primary.
1MRK 506 375-UEN A Section 7
Impedance protection
Railway application RER670 2.2 IEC 135
Application manual