ABB RER670 - Interlocking for Busbar Earthing Switch BB_ES; Application; Signals in Single Breaker Arrangement

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BH_LINE
(WA1)A1
(WA2)B1 B2
A2
en04000503.vsd
BH_LINE
BH_LINE BH_LINE
IEC04000503 V1 EN-US
Figure 111: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic is the same as for the logic for the double-breaker
configuration.
Signal
S1DC_OP All disconnectors on bus-section 1 are open.
S2DC_OP All disconnectors on bus-section 2 are open.
VPS1_DC The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB No transmission error from breaker and a half (BH) that contains the above
information.
12.4.7 Interlocking for busbar earthing switch BB_ES
IP14164-1 v4
12.4.7.1 Application
M15015-3 v7
The interlocking for busbar
earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure
112.
QC
en04000504.vsd
IEC04000504 V1 EN-US
Figure 112: Switchyard layout BB_ES
M15053-4 v4
The signals from other bays connected to the module BB_ES are described below.
12.4.7.2 Signals in single breaker arrangement
M15053-6 v5
The busbar earthing switch is only allowed to operate if all disconnectors of the
bus-section are open.
1MRK 506 375-UEN A Section 12
Control
Railway application RER670 2.2 IEC 279
Application manual