EasyManua.ls Logo

ABB RER670 - Signals from Bypass Busbar

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
QB1 QB2
QC1
QA1
QC2
QB9
QC9
WA1 (A)
WA2 (B)
WA7 (C)
QB7
en04000478.vsd
IEC04000478 V1 EN-US
Figure 84: Switchyard layout ABC_LINE
M13560-4 v5
The signals from other bays connected to the module ABC_LINE are described
below.
12.4.2.2 Signals from bypass busbar
M13560-6 v5
To derive the signals:
Signal
BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar
WA7
These signals from each line bay (ABC_LINE) except that of the own bay are
needed:
Signal
QB7OPTR Q7 is open
VPQB7TR The switch status for QB7 is valid.
EXDU_BPB No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
Section 12 1MRK 506 375-UEN A
Control
256 Railway application RER670 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RER670

Related product manuals