21.4.2 Setting guidelines
M15259-3 v4
The setting ActiveSetGrp, is used to select which parameter group to be active. The
active group can also be selected with configured input to the function block
SETGRPS.
The length of the pulse, sent out by the output signal SETCHGD when an active
group has changed, is set with the parameter t.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between. Only the selected number of setting groups will be available in
the Parameter Setting tool (PST) for activation with the ActiveGroup function
block.
21.5 Rated system frequency PRIMVAL
IP15064-1 v2
21.5.1 Identification
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Primary system values PRIMVAL - -
21.5.2 Application
M15288-3 v6
The rated system frequency and phase rotation direction are
set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.
21.5.3 Setting guidelines
M15292-3 v2
Set the system rated frequency. Refer to section
"Signal matrix for analog inputs
SMAI" for description on frequency tracking.
21.6 Global base values GBASVAL
GUID-2FDB0A2C-10FE-4954-B6E4-9DA2EEEF1668 v1
21.6.1 Identification
GUID-0D5405BE-E669-44C8-A208-3A4C86D39115 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Global base values GBASVAL - -
Section 21 1MRK 506 375-UEN A
Basic IED functions
466 Railway application RER670 2.2 IEC