to the function. In addition to that, the function generates alarms based on received
information.
15.3.3 Setting guidelines
GUID-0C8E498B-2A65-44ED-91D6-53EC72F49222 v2
The parameters for Liquid medium supervision SSIML can be set via local HMI or
Protection and Control Manager PCM600.
Operation
: This is used to disable/enable the operation of liquid medium
supervision i.e. Off/On.
LevelAlmLimit: This is used to set the limit for a level alarm condition in the
transformer.
LevelLOLimit: This is used to set the limit for a level lockout condition in the
transformer.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in
the transformer.
TempLOLimit: This is used to set the limit for a temperature lockout condition in
the transformer.
tLevelAlarm: This is used to set the time delay for a level alarm indication, given in
s.
tLevelLockOut: This is used to set the time delay for a level lockout indication,
given in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout
indication, given in s.
tResetLevelAlm: This is used for the level alarm indication to reset after a set time
delay in s.
tResetLevelLO: This is used for the level lockout indication to reset after a set time
delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a
set time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.