3.1.1.1 Description of configuration – transformer protection application in
compensated networks
GUID-29F96EB6-ABC0-4F35-87EF-88049138C405 v1
QB1
W1-QA1
WA1
RER670 V 2.2 – Application for Transformer Protection
¾-19“-Casing, 1xBIM, 1xSOM, 1xMIM 12AI (7I+5U)
CT
VT
BR PTOC
51 IBR>
SMP PTRC
94 10
VN MMXU
MET UN
FRW SPVC
U>/I<
L PTTR
26 θ>
CCRW RBRF
50BF 2I>BF
Temp.-Sensor
Other Functions available from the function library
optional Functions
ROV2 PTOV
59N 2(U0>)
S CSWI
3 Control
S XSWI
3 Control
S XCBR
3 Control
Q CRSV
3 Control
S CILO
3 Control
PH PIOC
50 2I>>
EFRW PIOC
50N IN>>
O2RW PTOV
59 2(2U>)
Q CBAY
3 Control
S SIML
71
W2-QA1
L2
VT
L1-L2
ZGT PDIS
21 Z<
C MSQI
MET Isqi
W1
W2
T1P PDIF
87T Id/I>
Transducer
D2 PTOC
51_67 2(2I>)
D2 PTOC
51_67 2(2I>)
L1, nicht benutzt
C MMXU
MET I
SA PTUF
81 f<
L2
CT
L2
CV MMXN
MET P/Q
TP PIOC
64 IN>>>
BF Prot.
C MMXU
MET I
D2 PTOC
51_67 2(2I>)
D2 PTOC
51_67 2(2I>)
FRW SPVC
U>/I<
CCRW RBRF
50BF 2I>BF
EF2 PTOC
51N_67N
2(IN>)
CV MMXN
MET P/Q
I> ASY
SA PTUF
81 f<
U2RW PTUV
27 2(2U<)
V MMXU
MET U
V MSQI
MET Usqi
VN MMXU
MET UN
SMP PTRC
94 10
SMP PTRC
94 10
SMP PTRC
94 10
SMP PTRC
94 10
SMP PTRC
94 10
Trip 1 HV Trip 2 HV Trip to BBP
Trip 1 LV Trip 2 LV Back-up prot.
4-20 mA
XENC POW
25T POW
67N
SDE PSDE
IN>
REF PDIF
87N IdN/I
L1
L2
T1P PDIF
87T Id/I>
long. Diff Prottransv. Diff Prot.
IEC17000009-1-en.vsdx
IEC17000009 V1 EN-US
Figure 2: Configuration diagram for transformer protection application in
compensated networks
Section 3 1MRK 506 375-UEN A
Configuration
38 Railway application RER670 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RER670