EasyManua.ls Logo

ABB RER670 - Page 183

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Where
I
j
is the capacitive earth fault current at a non-resistive phase-to-earth fault
X
c
is the capacitive reactance to earth
In a system with a neutral point resistor (resistance earthed system) the impedance
Z
0
can be calculated as:
0
2
2
cn
cn
j
XR
Z
j
XR


IECEQUATION16032 V1 EN-US (Equation 45)
Where
R
n
is the resistance of the neutral point resistor
In many systems there is also a neutral point reactor (Petersen coil) connected to
one or more transformer neutral points. In such a system the impedance Z
0
can be
calculated as:

0
4
//2 // 2
222
nnc
cn n
nc n n c
RXX
ZjXRjX
XX jR X X


IECEQUATION16033 V1 EN-US (Equation 46)
Where
X
n
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 2X
n
= X
c
In
this case the impedance Z
0
will be: Z
0
= 2R
n
Now consider a system with an earthing via a resistor giving higher earth fault
current than the high impedance earthing
. The series impedances in the system can
no longer be neglected. The system with a single phase to earth fault can be
described as in Figure
58.
1MRK 506 375-UEN A Section 8
Current protection
Railway application RER670 2.2 IEC 177
Application manual

Table of Contents

Other manuals for ABB RER670

Related product manuals