EasyManua.ls Logo

ABB RER670 - Page 268

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For bus-coupler bay n, these conditions are valid:
QB12OPTR (bay 1)
QB12OPTR (bay 2)
. . .
. . .
QB12OPTR (bay n-1)
&
BBTR_OP
VPQB12TR (bay 1)
VPQB12TR (bay 2)
. . .
. . .
VPQB12TR (bay n-1)
&
VP_BBTR
EXDU_12 (bay 1)
EXDU_12 (bay 2)
. . .
. . .
EXDU_12 (bay n-1)
&
EXDU_12
en04000481.vsd
IEC04000481 V1 EN-US
Figure 89: Signals from any bays in bus-coupler bay n
If the busbar is divided by bus-section disconnectors into bus-sections, the signals
BBTR are connected in parallel - if both bus-section disconnectors are closed. So
for the basic project-specific logic for BBTR above, add this logic:
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
ABC_BC
ABC_LINE ABC_BC
(WA1)A1
(WA2)B1
(WA7)C C
B2
A2
en04000482.vsd
AB_TRAFO
IEC04000482 V1 EN-US
Figure 90: Busbars divided by bus-section disconnectors (circuit breakers)
The following signals from each bus-section disconnector bay (A1A2_DC) are
needed. For B1B2_DC, corresponding signals from busbar B are used. The same
type of module (A1A2_DC) is used for different busbars, that is, for both bus-
section disconnector A1A2_DC and B1B2_DC.
Signal
DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-
section coupler bay (A1A2_BS), rather than the bus-section disconnector bay
(A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B
Section 12 1MRK 506 375-UEN A
Control
262 Railway application RER670 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RER670

Related product manuals